Skip to main content
SearchLoginLogin or Signup

Review 2: "SARS-CoV-2 Aerosol Transmission in Schools: The Effectiveness of Different Interventions"

Reviewers find this a straightforward modelling study, though ask for clarification on some assumptions and emphasize that the results may apply only to naturally-ventilated classrooms.

Published onSep 19, 2021
Review 2: "SARS-CoV-2 Aerosol Transmission in Schools: The Effectiveness of Different Interventions"
1 of 2
key-enterThis Pub is a Review of
SARS-CoV-2 aerosol transmission in schools: the effectiveness of different interventions
Description

AbstractBackgroundIndoor aerosol transmission of SARS-CoV-2 has been widely recognized, especially in schools where children remain in closed indoor spaces and largely unvaccinated. Measures such as strategic natural ventilation and high efficiency particulate air (HEPA) filtration remain poorly implemented and mask mandates are often progressively lifted as vaccination rollout is enhanced.MethodsWe adapted a previously developed aerosol transmission model to study the effect of interventions (natural ventilation, face masks, HEPA filtration, and their combinations) on the concentration of virus particles in a classroom of 160 m3 containing one infectious individual. The cumulative dose of viruses absorbed by exposed occupants was calculated.ResultsThe most effective single intervention was natural ventilation through the full opening of six windows all day during the winter (14-fold decrease in cumulative dose), followed by the universal use of surgical face masks (8-fold decrease). In the spring/summer, natural ventilation was only effective (≥ 2-fold decrease) when windows were fully open all day. In the winter, partly opening two windows all day or fully opening six windows at the end of each class was effective as well (≥ 2-fold decrease). Opening windows during yard and lunch breaks only had minimal effect (≤ 1.2-fold decrease). One HEPA filter was as effective as two windows partly open all day during the winter (2.5-fold decrease) while two filters were more effective (4-fold decrease). Combined interventions (i.e., natural ventilation, masks, and HEPA filtration) were the most effective (≥ 30-fold decrease). Combined interventions remained highly effective in the presence of a super-spreader.ConclusionsNatural ventilation, face masks, and HEPA filtration are effective interventions to reduce SARS-CoV-2 aerosol transmission. These measures should be combined and complemented by additional interventions (e.g., physical distancing, hygiene, testing, contact tracing, and vaccination) to maximize benefit.

RR:C19 Evidence Scale rating by reviewer:

  • Reliable. The main study claims are generally justified by its methods and data. The results and conclusions are likely to be similar to the hypothetical ideal study. There are some minor caveats or limitations, but they would/do not change the major claims of the study. The study provides sufficient strength of evidence on its own that its main claims should be considered actionable, with some room for future revision.

***************************************

Review:

The manuscript “SARS-CoV-2 Aerosol Transmission in Schools: the Effectiveness of Different Interventions” describes the results of modelling SARS-Co-V-2 virion exposure dose within classrooms using the COVID Airborne Risk Assessment (CARA) tool, assuming 1 infected person standing within the room over the course of a school day. The interventions considered include 1) open windows, 2) installation of portable HEPA filters, and 3) use of masks on occupants. Reductions in virion accumulation rates under combinations of these intervention methods are compared to estimated virion accumulations in an unventilated comparison classroom scenario. The authors report that opening 6 classroom windows generates a 14-fold reduction in exposure during winter and a 2-fold reduction during spring/summer; approximately the same as opening two windows fully during winter. Masks use results in an 8-fold reduction. HEPA filters in combination with partially opened windows yielded a 2.5-to-4-fold reduction. All interventions combined resulted in an approximate 30-fold decrease. The premise of the modelling and conclusions are, in my opinion appropriate, important, and the article is worthy of publication with the following clarifications, which in my view are necessary for practical consideration and application by readers:

  1. The assumptions within the modelling are that the classrooms have no mechanical ventilation, but are instead ventilated solely by windows along one side. This is true in many older school buildings, as well as converted church-to school buildings throughout the U.S., making this a valid and important subject for study. Therefore, the article should specify that this modelling was for naturally ventilated classrooms, not mechanically ventilated ones. I recommend that the title be revised to address this. The revised tittle for consideration is “SARS-CoV-2 Aerosol Transmission in Schools: the Effectiveness of Different Interventions in Naturally Ventilated Classrooms.”

  2. The above, notwithstanding, many schools have mechanical ventilation which may include unit ventilators along the window wall, or overhead HVAC supply and return registers serviced by rooftop air handling units. It is our experience in assessing hundreds of schools and classrooms throughout New Jersey, New York and Pennsylvania, that total airflow and outdoor air introduction rates from these mechanical ventilation systems vary greatly dependent upon factors such as design specifications, vintage, state of repair, filters installed, thermostat programming and other factors.

  3. For these mechanical ventilation systems, the outdoor air introduction rates may vary from 0 to 100% depending on condition, thermostat settings, outdoor air temperature linkage position etc. Pre-COVID these were often set to a minimum outdoor air introduction rate of 10-15%, and many are now being increased to comply with recent CDC and ASHRAE COVID recommendations. Most mechanical ventilation systems have modest filter efficiencies, (MERV 8-11 at best).

  4. Based upon points 2 and 3 above, and because the authors use the difference in outdoor versus indoor temperatures (√ΔT) as the driving factor for outdoor air introduction rates via windows, I suggest that the authors report the outdoor air introduction rates in (cubic feet per minute (cfm) as well as in Air Changes per Hour (ACH) computed by the CARA model under each of the winter versus spring/summer seasons (under both the 6 windows fully open as well as 2 windows partially open scenarios) so that readers can apply the implications of the findings to conditions in naturally and mechanically ventilated classrooms as described in discussion point #5 below.

  5. The discussion of CO2 as a measure of natural ventilation is based upon the ASHRAE 62 guidelines which indicate bio-effluents within occupied buildings are diluted to acceptable ranges when outdoor air introduction rates exceed approximately 15 cubic feet per minute per person. So for a 160m^3 typical classroom servicing as an example 20-25 persons, outdoor air introduction rates of approximately 300-375 cubic feet per minute (cfm) would be recommended as the minimum outdoor introduction rate. At steady state equilibrium conditions, this level of outdoor air introduction would be expected to result in indoor CO2 concentrations of less than 1,000 parts per million (assuming outdoor air contained approximately 300 ppm CO2). While the underlying equations that yield these results are beyond the scope of this paper, the authors should make the link between indoor CO2 and ventilation rates clear.

    All combined, it is my professional opinion that these clarifications will help readers better; 1) understand the implications of the study, 2) applicability of the study to naturally ventilated classrooms, 3) applicability to mechanically ventilated classrooms, and 4) steps which can be taken to attenuate COVID-19 transmission risks when mechanically ventilation systems fail due to broken parts, failed motors or when fresh air dampers are closed.

    References: 1.Assess Ventilation When Determining Safe Distancing in Schools to Control Coronavirus Disease 2019 (COVID-19) Transmission Richard M Lynch, Elissa Favata, Michael Gochfeld Clinical Infectious Diseases, ciab353, https://doi.org/10.1093/cid/ciab353


Comments
2
?
willd Robrt:

Selecting the right HVAC system https://linktr.ee/ecoplumbinghvac depends on several factors, including the size of your home, your climate, and your energy efficiency goals. Professional guidance is crucial to ensure you choose a system that meets your needs while staying within your budget.

sgfddfyhjyh [email protected]:

Repairing these elements can refresh the look of your home, enhancing its curb appeal and making it more visually appealing to residents and visitors Windows repair greenville.